Strany 1 - EtherNet/IP

EtherNet/IPIAI America Inc. Operation Manual, Fourth EditionACON-C/CGPCON-C/CG/CA/CFASCON-CA

Strany 2

2No.Operation Description Description 2 Transportation Ɣ When carrying a heavy object, do the work with two or more persons or utilize equipment su

Strany 3 - Please Read Before Use

3. SCON-CA/CFA923.5.4 Setting the Subnet Mask Set parameter No. 141, “SNMK: Subnet mask.” Set the same value you have set in the master unit and

Strany 4

3. SCON-CA/CFA933.6 Communicating with the Master Station 3.6.1 Operation Modes and Corresponding PLC I/O Areas The addresses allocated for each ope

Strany 5 - Table of Contents

3. SCON-CA/CFA94x PCON-CA/CFA outputoPLC input side (* “n” indicates the first input address of each axis.) DO on the PCON-CA/CFA side and output dat

Strany 6

3. SCON-CA/CFA953.6.2 Remote I/O Mode (Number of Occupied Bytes: 2) In this operation method, EtherNet/IP communications is used to mimic the operati

Strany 7

3. SCON-CA/CFA96(1) PLC address configuration (* “n” indicates the first address of each axis.) Parameter No.84PCON-CA/CFA side DI (Port No.) PLC sid

Strany 8

3. SCON-CA/CFA97(3) I/O signal assignment The controller's I/O port signal varies depending on the parameter No. 25 setting. (Refer to operation

Strany 9 - Safety Guide

3. SCON-CA/CFA98Parameter No. 25 setting 512-point mode Electromagnetic valve mode 1 Electromagnetic valve mode 23 4 5 Category Port No. Symbol Si

Strany 10

3. SCON-CA/CFA993.6.3 Position/Simplified Direct Value Mode (Number of Occupied Bytes: 8) In this operation mode, EtherNet/IP communication is used t

Strany 11

3. SCON-CA/CFA100(2) I/O signal allocation for each axis The I/O signals of each axis consist of four input words (4 words = 8 bytes) and four output

Strany 12

3. SCON-CA/CFA101PLC input Address (* “n” indicates the first input address of each axis.) When the current position is shown using the negative figur

Strany 13

3No.Operation Description Description (2) Cable Wiring Ɣ Use our company’s genuine cables for connecting between the actuator and controller, and for

Strany 14

3. SCON-CA/CFA102(3) I/O signal assignment (* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Co

Strany 15 - Alert Indication

3. SCON-CA/CFA103(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents Details Current pos

Strany 16 - Handling Precautions

3. SCON-CA/CFA1043.6.4 Half Direct Value Mode (Number of Occupied Bytes: 16) This is the operation mode with the target position, positioning band, s

Strany 17 - 1. Overview

3. SCON-CA/CFA105(2) I/O signal allocation for each axis The I/O signals of each axis consist of one input word (8 words = 16 bytes) and one output w

Strany 18 - 1. Overview

3. SCON-CA/CFA106PLC output Address (* “n” indicates the first output address of each axis.) When the target position is shown using the negative figu

Strany 19 - 2. ACON-C/CG, PCON-C/CG

3. SCON-CA/CFA107PLC input Address (* “n” indicates the first input address of each axis.) When the current position is shown using the negative figur

Strany 20 - 2. ACON-C/CG, PCON-C/CG

3. SCON-CA/CFA108(3) I/O signal assignment (* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Co

Strany 21

3. SCON-CA/CFA109(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents DetailsPressing cur

Strany 22 - 2.2 Model Numbers

3. SCON-CA/CFA110(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents Details Current pos

Strany 23 - /5 .'&

3. SCON-CA/CFA1113.6.5 Full Direct Value Mode (Number of Occupied Bytes: 32) This is the operation mode with all the values (target position, speed,

Strany 24

4No.Operation Description Description 4 Installation and Start(4) Safety Measures Ɣ When the work is carried out with 2 or more persons, make it cle

Strany 25 - 2.4.1 Connection Diagram

3. SCON-CA/CFA112(2) I/O signal allocation for each axis The I/O signals of each axis consist of one input word (16 words = 32 bytes) and one output

Strany 26 - 2.5.2 Setting the Baud Rate

3. SCON-CA/CFA113PLC output Address (* “n” indicates the first output address of each axis.) When the target position is shown using the negative figu

Strany 27

3. SCON-CA/CFA114Address (* “n” indicates the first output address of each axis.) When the zone boundary is shown using the negative figure, it is exp

Strany 28

3. SCON-CA/CFA115PLC input Address (* “n” indicates the first input address of each axis.) When the current position is shown using the negative figur

Strany 29

3. SCON-CA/CFA116Address (* “n” indicates the first input address of each axis.) 1 word = 2 bytes = 16 bits n+20, n+21 b15 b14 b13 b12 b11 b10

Strany 30

3. SCON-CA/CFA117(3) I/O signal assignment (* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Co

Strany 31

3. SCON-CA/CFA118(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Address Bit Symbol Function DetailsAcceleration 16-

Strany 32 - ACON

3. SCON-CA/CFA119(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Address Bit Symbol Function Detailsb2 DIR Pressing

Strany 33

3. SCON-CA/CFA120(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents DetailsCurrentposit

Strany 34 - PCON

3. SCON-CA/CFA121(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents Detailsb15 EMGS Em

Strany 35

5No.Operation Description Description 6 Trial Operation Ɣ When the work is carried out with 2 or more persons, make it clear who is to be the leade

Strany 36

3. SCON-CA/CFA1223.6.6 Remote I/O Mode 2 (Number of Occupied Bytes: 12) In this operation method, EtherNet/IP communications is used to mimic the ope

Strany 37

3. SCON-CA/CFA123(1) PLC address configuration (* “n” indicates the first address of each axis.) Parameter No.84PCON-CA/CFA side DI and input regis

Strany 38

3. SCON-CA/CFA124PLC input Address (* “n” indicates the first input address of each axis.) When the current position is shown using the negative figur

Strany 39

3. SCON-CA/CFA125(3) I/O signal assignment For the signal assignments corresponding to each PIO pattern, refer to the I/O signal assignments for the

Strany 40

3. SCON-CA/CFA1263.6.7 I/O Signal Controls and Function * ON indicates that the applicable bit signal is “1”, while OFF indicates that the bit signal

Strany 41

3. SCON-CA/CFA127(5) Servo ON command (SON) PLC output signal Operation preparation end (SV) PLC input signal When the SON signal is turned ON, t

Strany 42

3. SCON-CA/CFA128(6) Home return (HOME) PLC output signal Home return completion (HEND) PLC input signal Under home return operation (GHMS) PLC

Strany 43

3. SCON-CA/CFA129(7) Positioning start (CSTR): Used in the position/simple direct mode PLC output signal This signal is processed at the startup (ON

Strany 44

3. SCON-CA/CFA130TravelSpeedPositioning band TimeTarget position Timing at which the position complete signal turns ON (10) Positioning completion sig

Strany 45

3. SCON-CA/CFA131Zone signal+ direction Actuator operation Home Zone setting -Zone setting +(12) Zone 1 (ZONE1) PLC input signal Zone 2 (ZONE2)

Strany 46

6No.Operation Description Description 8 Maintenance and Inspection Ɣ When the work is carried out with 2 or more persons, make it clear who is to be

Strany 47

3. SCON-CA/CFA132(13) +Jog (JOG+) PLC output signal –Jog (JOG–) PLC output signal This signal is the command for the jog operation startup or inch

Strany 48

3. SCON-CA/CFA133(14) Jog-speed/inch-distance switching (JVEL) PLC output signal This change-over signal is used for the parameters specifying the jo

Strany 49

3. SCON-CA/CFA134(16) Teaching mode command (MODE) PLC output signal Teaching mode signal (MODES) PLC input signal When the MODE signal is turned

Strany 50

3. SCON-CA/CFA135SpeedTravelPositioning band Positioning band Positioning band DIR = OFF Target position DIR = ON (19) Operating mode selector (RMOD)

Strany 51

3. SCON-CA/CFA136(23) Pressing and a miss (PSFL) PLC input signal In the case that the pressing operation was performed, and the actuator moved the

Strany 52

3. SCON-CA/CFA137(26) Load output judgment (LOAD) PLC input signal This signal is available only in the pressing operation. When this signal is used f

Strany 53

3. SCON-CA/CFA138Target positionTravelSpeedPosition where the actuator is pushed against the work part and the pressing completion is judged so the po

Strany 54

3. SCON-CA/CFA139(28) Stopping control mode (SMOD) PLC output signal One of the pulse motor general characteristics is that that the holding curren

Strany 55

3. SCON-CA/CFA140Setting: 50 Setting: 100Setting: 10 (29) Acceleration/deceleration mode (MOD1ޔMOD0) PLC output signal This signal is used to select t

Strany 56

3. SCON-CA/CFA141Caution: [1] Even if a position command or direct value command with S-shaped motion setting is issued when the actuator is running,

Strany 57

7Alert Indication The safety precautions are divided into “Danger”, “Warning”, “Caution” and “Notice” according to the warning level, as follows, and

Strany 58

3. SCON-CA/CFA142(30) Stop Mode Selection (ASO1, ASO0) PLC Output Signal Select the stop mode for the duration before the movement to the next posi

Strany 59

3. SCON-CA/CFA143PLC sequence programControl signalStatus signalPCON Control signalStatus signalMaster station o Slave transmission de

Strany 60

3. SCON-CA/CFA1443.8 Operation The timings for the basic operation examples in the Position/Simplified Direct Value Mode, Half direct value mode and

Strany 61

3. SCON-CA/CFA145* T1: Considering the scanning time of the host controller, set it so that “T1  0ms”. * Yt+Xt  tdpf  Yt+Xt+3 (msec) [7][1][2][3][

Strany 62

3. SCON-CA/CFA146(2) Operation in the half direction mode It is operated with the data set in the PLC's target position register, positioning ba

Strany 63

3. SCON-CA/CFA147*T1: Considering the scanning time of the host controller, set it so that “T1  0ms”. *Yt+Xt  tdpf  Yt+Xt+3(msec) Positioning band

Strany 64

3. SCON-CA/CFA148(3) Operation in the full direct mode The actuator is operated by specifying all conditions required for positioning such as the tar

Strany 65

3. SCON-CA/CFA149[1][2][3][4][5][6][7][8]Set value of target position data Set value of positioning band data Set value of speed data Set value of pos

Strany 66

3. SCON-CA/CFA150*T1: Considering the scanning time of the host controller, set it so that “T1  0ms”. *Yt+Xt  tdpf  Yt+Xt+3 (msec) [9][10][11][12]

Strany 67

3. SCON-CA/CFA151[1][2][3]Actuator speed Speed n2 Speed n3 Set value of speed or acceleration/deceleration (4) Data change during movement In the hal

Strany 68

8Handling Precautions 1. It is recommended that the baud rate be set based on auto negotiation. Make sure the link setting of the EtherNet/IP unit m

Strany 69

3. SCON-CA/CFA1523.9 EtherNet/IP Related Parameters Parameters relating to EtherNet/IP are No. 84, No. 86 to 87, No. 90, No. 140 to 142 and No. 159.

Strany 70

3. SCON-CA/CFA153z Network type (No.87 NTYP) The network module type is set for the parameter No. 87. Do not change the default value. z Field I/O f

Strany 71

3. SCON-CA/CFA154(Example ii) Set value = “1” z indicates ON, while c indicates OFF PCON Inputresister PCON Outputresister Hexadecimaldata Hexadecima

Strany 72

3. SCON-CA/CFA155(Example iii) Set value = “2” z indicates ON, while c indicates OFF PCON Inputresister PCON Outputresister Hexadecimaldata Hexadecim

Strany 73

3. SCON-CA/CFA156(Example iv) Set value = “3” z indicates ON, while c indicates OFF PCON Inputresister PCON Outputresister Hexadecimaldata Hexadecima

Strany 74

3. SCON-CA/CFA157z IP address (No. 140: IPAD) Specify the IP address in parameter No. 140. Setting range: 0.0.0.0 to 255.255.255.255 (Factory set

Strany 75

4. SCON-CA1584. SCON-CA 4.1 Operation Modes and Functions SCON-CA controllers supporting Ethernet/IP can be operated in a desired operation mode sel

Strany 76

4. SCON-CA159[2] Position/simple direct mode: In this mode, the actuator is operated by specifying position numbers. You can select whether to specif

Strany 77

4. SCON-CA160[4] Full direct mode: In this mode, the actuator is operated by specifying all values relating to position control (target position, spe

Strany 78 - 2.7 I/O Signal Timings

4. SCON-CA161[7] Half direct mode 2: In this mode, the actuator is operated by specifying the speed, acceleration/deceleration and pressing current,

Strany 79 - 2.8 Operation

1. Overview91. Overview EtherNet/IP is an open field network. It is a standardized global open network specified by the IEC 61158 series of internati

Strany 80

4. SCON-CA1624.2 Model Numbers The model numbers of SCON-CA controller supporting EtherNet/IP are indicated as follows, respectively: z SCON-CA--EP

Strany 81

4. SCON-CA1634.3 EtherNet/IP Interface 4.3.1 Names of the Parts The names of each section related to EtherNet/IP are described as follows. NS LEDEth

Strany 82

4. SCON-CA1644.3.2 Monitor LED Indications The slave condition (each controller), as well as network condition, can be checked using the two LEDs, MS

Strany 83

4. SCON-CA1654.4 Wiring 4.4.1 Connection Diagram * Ethernet cable: Straight cable of category 5e or above, 100 m max (Aluminum tape and braided doub

Strany 84

4. SCON-CA1664.5 Setting Using the teaching tool, set controller parameters. Set the mode toggle switch on the front panel of the controller to “MANU

Strany 85

4. SCON-CA1674.5.3 Setting the IP Address Set parameter No. 140, “IPAD: IP address.” [Refer to 4.9, “EtherNet/IP Parameters.”] Settable Range:0

Strany 86

4. SCON-CA1684.6 Communicating with the Master Station 4.6.1 Operation Modes and Corresponding PLC I/O Areas The channels allocated for each operati

Strany 87

4. SCON-CA169x PLC output o SCON-CA input side (* “n” indicates the byte address of each axis.) DO on the SCON-CA side and output data register Posit

Strany 88

4. SCON-CA170x SCON-CA output o PLC input (* “n” indicates the byte address of each axis.) DO on the SCON-CA side and output data register Remote I/O

Strany 89

4. SCON-CA171x SCON-CA outputoPLC input Side (* “n” indicates the byte address of each axis.) DO on the SCON-CA side and output data register Positio

Strany 90

1. Overview101.1 EtherNet/IP Specifications Item Specification Communication standards IEC61158 (IEEE802.3) Baud rate 10BASE-T/100 BASE-T (Auto n

Strany 91

4. SCON-CA1724.6.2 Remote I/O Mode (Number of Occupied Bytes: 2) This is the operation mode with the position No. set up as the same as using PIO (24

Strany 92 - 2.10 Troubleshooting

4. SCON-CA173(1) PLC address configuration (* “n” indicates the node address of each axis.) Parameter No.84SCON-CA side DI(Port No.) PLC side output

Strany 93 - 3. PCON-CA/CFA

4. SCON-CA174(3) I/O signal assignment The controller's I/O port signal varies depending on the parameter No. 25 setting. (Refer to Operation Ma

Strany 94

4. SCON-CA175Parameter No. 25 setting 512-point mode Electromagnetic valve mode 1 Electromagnetic valve mode 23 4 5 Category Port No. Symbol Sig

Strany 95

4. SCON-CA176Setting of parameter No. 25 Force control mode 1 Force control mode 2 6 7 Category Port No. Symbol Signal name Symbol Signal name 0

Strany 96 - 3.2 Model Numbers

4. SCON-CA1774.6.3 Position/Simplified Direct Value Mode (Number of Occupied Bytes: 8) This is the operation mode with the position No. set up. Wheth

Strany 97 - 3.3.1 Names of the Parts

4. SCON-CA178 (2) I/O Signal Allocation for each Axis The I/O signals of each axis consist of four input words (4 words = 8 bytes) and four output wo

Strany 98 - 3.4.1 Connection Diagram

4. SCON-CA179PLC input Address (* “n” indicates the node address of each axis.) When the current position is shown using the negative figure, it is ex

Strany 99 - 3.5.2 Setting the Baud Rate

4. SCON-CA180(3) I/O signal assignment (* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal Type Bit Symbol Conten

Strany 100 - 3. SCON-CA/CFA

4. SCON-CA181(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal Type Bit Symbol Contents Details Current positio

Strany 101

2. ACON-C/CG, PCON-C/CG112. ACON-C/CG, PCON-C/CG 2.1 Operation Modes and Functions ACON and PCON controllers equipped with EtherNet/IP can be operat

Strany 102

4. SCON-CA1824.6.4 Half Direct Value Mode (Number of Occupied Bytes: 16) This is the operation mode with the target position, positioning band, speed

Strany 103

4. SCON-CA183(2) I/O Signal Allocation for each Axis The I/O signals of each axis consist of one input word (8 words = 16 bytes) and one output word

Strany 104

4. SCON-CA184PLC output Address (* “n” indicates the node address of each axis.) When the target position is shown using the negative figure, it is ex

Strany 105 - (3) I/O signal assignment

4. SCON-CA185PLC input Address (* “n” indicates the node address of each axis.) When the current position is shown using the negative figure, it is ex

Strany 106

4. SCON-CA186(3) I/O signal assignment (* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Conten

Strany 107

4. SCON-CA187(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents Details Pressingcurrent

Strany 108

4. SCON-CA188(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents Details Currentposition

Strany 109

4. SCON-CA1894.6.5 Full Direct Value Mode (Number of Occupied Bytes: 32) This is the operation mode with all the values (target position, speed, etc.

Strany 110

4. SCON-CA190(2) I/O Signal Allocation for each Axis The I/O signals of each axis consist of one input word (16 words = 32 bytes) and one output word

Strany 111

4. SCON-CA191PLC output Address (* “n” indicates the node address of each axis.) When the target position is shown using the negative figure, it is ex

Strany 113

2. ACON-C/CG, PCON-C/CG12[2] Position/simplified direct value mode: In this operation mode, EtherNet/IP communication is used to select and command

Strany 114

4. SCON-CA192Address (* “n” indicates the node address of each axis.) When the zone boundary is shown using the negative figure, it is expressed using

Strany 115

4. SCON-CA193PLC input Channel (* “n” indicates the node address of each axis.) When the current position is shown using the negative figure, it is ex

Strany 116

4. SCON-CA194 b15n+18, n+19 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b032,768 16,384 8,192 4,096 2,048 1,024 512 256 128 64 32 16 8 4 2 1b15 b14

Strany 117

4. SCON-CA195(3) I/O signal assignment (* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Conten

Strany 118

4. SCON-CA196(* In the table, ON indicates that the applicable bit is “1,” while OFF indicates that the applicable bit is “0.”) Address Bit Symbol

Strany 119

4. SCON-CA197(* In the table, ON indicates that the applicable bit is “1,” while OFF indicates that the applicable bit is “0.”) Address Bit Symbol

Strany 120

4. SCON-CA198(* In the table, ON indicates that the applicable bit is “1,” while OFF indicates that the applicable bit is “0.”) Signal type Bit Symb

Strany 121

4. SCON-CA199(* In the table, ON indicates that the applicable bit is “1,” while OFF indicates that the applicable bit is “0.”) Signal type Bit Symb

Strany 122

4. SCON-CA2004.6.6 Remote I/O Mode 2 (Number of Occupied Bytes: 12) This is the operation mode with the position No. set up as the same as using PIO

Strany 123

4. SCON-CA201(1) PLC address configuration (* “n” indicates the node address of each axis.) Parameter No. 84 SCON-CA side DI and input register PLC

Strany 124

2. ACON-C/CG, PCON-C/CG13[4] Full direct value mode: In this operation mode, all values regarding position control (“Target Position,” "Speed”

Strany 125

4. SCON-CA202PLC input Address (* “n” indicates the node address of each axis.) When the current position is shown using the negative figure, it is ex

Strany 126

4. SCON-CA203(3) I/O signal assignment For the signal assignments corresponding to each PIO pattern, refer to the I/O signal assignments for the remo

Strany 127

4. SCON-CA2044.6.7 Position/Simplified Direct Value Mode2 (Number of Occupied Bytes: 8) In this mode, the actuator is operated by means of force con

Strany 128

4. SCON-CA205(2) I/O Signal Allocation for each Axis The I/O signals of each axis consist of one input word (4 words = 8 bytes) and one output word i

Strany 129

4. SCON-CA206PLC input Address (* “n” indicates the node address of each axis.) When the current position is shown using the negative figure, it is ex

Strany 130

4. SCON-CA207(3) I/O signal assignments(* In the table, ON indicates that the applicable bit is “1,” while OFF indicates that the applicable bit is

Strany 131

4. SCON-CA208(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents Details Currentposition

Strany 132

4. SCON-CA2094.6.8 Half Direct Value Mode 2 (Number of Occupied Bytes: 16) In this mode, the actuator is operated by means of force control (pressing

Strany 133

4. SCON-CA210(2) I/O Signal Allocation for each Axis The I/O signals of each axis consist of one input word (8 words = 16 bytes) and one output word

Strany 134

4. SCON-CA211PLC output Address (* “n” indicates the node address of each axis.) When the target position is shown using the negative figure, it is ex

Strany 135

2. ACON-C/CG, PCON-C/CG142.2 Model Numbers The Model numbers of ACON and PCON applicable to EtherNet/IP are described as follows. Ɣ ACON-C/CG--EP-

Strany 136

4. SCON-CA212PLC input Address (* “n” indicates the node address of each axis.) When the current position is a negative figure, it is expressed using

Strany 137

4. SCON-CA213(3) I/O signal assignment(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Content

Strany 138

4. SCON-CA214(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents Details Pressing current

Strany 139

4. SCON-CA215(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents Details Currentposition

Strany 140

4. SCON-CA2164.6.9 Remote I/O Mode 3 (Number of Occupied Bytes: 12) In this mode, force control (feedback pressing of load cell values) is used in ad

Strany 141

4. SCON-CA217(1) PLC address configuration (* “n” indicates the node address of each axis.) Parameter No. 84 SCON-CA side DI and input register PLC

Strany 142

4. SCON-CA218PLC input Address (* “n” indicates the node address of each axis.) When the current position is shown using the negative figure, it is ex

Strany 143

4. SCON-CA219(3) I/O signal assignment For the signal assignments corresponding to each PIO pattern, refer to the I/O signal assignments for the remo

Strany 144

4. SCON-CA2204.6.10 Half Direct Value Mode 3 (Number of Occupied Bytes: 16) In this mode, the jog function in the half direct numerical mode is not a

Strany 145

4. SCON-CA221(2) I/O Signal Allocation for each Axis The I/O signals of each axis consist of one input word (8 words = 16 bytes) and one output word

Strany 146

2. ACON-C/CG, PCON-C/CG152.3 EtherNet/IP Interface 2.3.1 Names of the Parts The names of each section related to EtherNet/IP are described as follow

Strany 147

4. SCON-CA222PLC output Address (* “n” indicates the node address of each axis.) When the target position is shown using the negative figure, it is ex

Strany 148

4. SCON-CA223PLC input Address (* “n” indicates the node address of each axis.) When the current position is shown using the negative figure, it is ex

Strany 149

4. SCON-CA224(3) I/O signal assignment(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Content

Strany 150 - Function

4. SCON-CA225(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Description Details Pressingcurr

Strany 151 - 3.7 I/O Signal Timings

4. SCON-CA226(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents Details Currentposition

Strany 152 - 3.8 Operation

4. SCON-CA2274.6.11 I/O Signal Controls and Function * ON indicates that the applicable bit signal is “1”, while OFF indicates that the bit signal i

Strany 153

4. SCON-CA228(5) Servo ON command (SON) PLC output signal Operation preparation end (SV) PLC input signal When the SON signal is turned ON, the s

Strany 154

4. SCON-CA229(6) Home return (HOME) PLC output signal Home return completion (HEND) PLC input signal Under Home return Operation (GHMS) PLC inpu

Strany 155 - Pressing

4. SCON-CA230(7) Positioning start (CSTR):Used in the position/simple direct mode PLC output signal This signal is processed at the startup (ON ed

Strany 156

4. SCON-CA231(10) Positioning completion signal (PEND) PLC input signal This signal is turned “ON” when the actuator is moved to the target posit

Strany 157

2. ACON-C/CG, PCON-C/CG162.3.2 Monitor LED Indications The slave condition (each controller), as well as network condition, can be checked using the

Strany 158

4. SCON-CA232(12) Zone 1 (ZONE1) PLC input signal Zone 2 (ZONE2) PLC input signal Position zone (PZONE) PLC input signal These signals are turned O

Strany 159

4. SCON-CA233(13) +Jog (JOG+) PLC output signal –Jog (JOG–) PLC output signal This signal is the command for the jog operation startup or inching op

Strany 160

4. SCON-CA234(14) Jog-speed/inch-distance switching (JVEL) PLC output signal This change-over signal is used for the parameters specifying the jo

Strany 161

4. SCON-CA235(16) Teaching mode command (MODE) PLC output signal Teaching mode signal (MODES) PLC input signal When the MODE signal is turned “ON”

Strany 162

4. SCON-CA236(19) Operating mode selector (RMOD) PLC output signal Operation Mode Status (RMDS) PLC input signal The operation mode is selecte

Strany 163

4. SCON-CA237(23) Pressing and a miss (PSFL) PLC input signal In the case that the pressing operation was performed, and the actuator moved the t

Strany 164

4. SCON-CA238(26) Load output judgment (LOAD) PLC input signal This signal is available only in the pressing operation. When this signal is used fo

Strany 165 - 3.10 Troubleshooting

4. SCON-CA239(27) Torque level (TRQS) PLC input signal This signal is available only in the pressing operation. When the motor current reaches th

Strany 166 - Communication

4. SCON-CA240(28) Absolute battery voltage low 2arning (BALM) PLC input signal With an absolute system, this signal is OFF when the absolute battery

Strany 167

4. SCON-CA241(30) Acceleration/deceleration mode (MOD1, MOD0) PLC output signal This signal is used to select the acceleration/deceleration pattern

Strany 168 - Position No. 0

2. ACON-C/CG, PCON-C/CG17812.4 Wiring Example 2.4.1 Connection Diagram * Ethernet cable: Straight cable of category 5e or above, 100 m max (Aluminu

Strany 169

4. SCON-CA242First-Order Lag Filter This describes much gentle acceleration/deceleration curve than that for the linear acceleration/deceleration (t

Strany 170 - 4.2 Model Numbers

4. SCON-CA243(31) Standstill mode selection (ASO0, ASO1) PLC output signals Select the stop mode to be applied while the actuator is standing by to

Strany 171 - 4.3.1 Names of the Parts

4. SCON-CA244(32) Load cell calibration command (CLBR) PLC output signal Load cell calibration complete (CEND) PLC input signal The factory settin

Strany 172 - 4. SCON-CA

4. SCON-CA2454.7 I/O Signal Timings When any of the control signal is turned ON to perform the operation of the actuator using the PLC's sequenc

Strany 173 - 4.4.1 Connection Diagram

4. SCON-CA2464.8 Operation The timings for the basic operation examples in the Position/Simplified Direct Value Mode 1 and 2 , Half Direct Value Mode

Strany 174 - 4.5.2 Setting the Baud Rate

4. SCON-CA247*T1: Considering the scanning time of the host controller, set it so that “T1  0ms”. *Yt+Xt  tdpf  Yt+Xt+3(msec) [1][2]Set value of ta

Strany 175

4. SCON-CA248(2) Operation in the half direction mode 1 to 3 It is operated with the data set in the PLC's target position register, positioning

Strany 176

4. SCON-CA249*T1: Considering the scanning time of the host controller, set it so that “T1  0ms”. *Yt+Xt  tdpf  Yt+Xt+3(msec) Set value of target p

Strany 177

4. SCON-CA250(3) Operation in the full direct mode The actuator is operated by specifying all conditions required for positioning such as the target

Strany 178

4. SCON-CA251Set value of target position data [1][2]Set value of positioning band data Set value of speed data [3][4][5][6][7][8]Set value of positio

Strany 179

2. ACON-C/CG, PCON-C/CG182.5 Setting Using the teaching tool, set controller parameters. Set the mode toggle switch on the front panel of the control

Strany 180

4. SCON-CA252* T1: Considering the scanning time of the host controller, set it so that “T1  0ms”. * Yt+Xt  tdpf  Yt+Xt+3(msec) [9]Positioning ban

Strany 181

4. SCON-CA253(4) Data change during movement In the half direct mode or full direct mode 1 to 3, the value currently set to a given resister among th

Strany 182

4. SCON-CA2544.9 EtherNet/IP Related Parameters Parameters relating to EtherNet/IP are No. 84 to No. 87, No. 90, No. 140 to No. 142 and No.159. .Cate

Strany 183

4. SCON-CA255z Fieldbus baud rate (No. 86: FBRS) Specify the baud rate in parameter No. 86. Set value Baud rate 0 (Factory setting) Auto negotia

Strany 184

4. SCON-CA256z Field I/O format (No.90 FMIO) Addresses in the PLC are assigned in units of 16 points (2 bytes) based on the node address set in the co

Strany 185

4. SCON-CA257(Example ii) Set value = “1” z indicates ON, while c indicates OFF SCON Inputresister SCON OutputresisterHexadecimal dataPLC:OutputCHPLC

Strany 186

4. SCON-CA258(Example iii) Set value = “2” z indicates ON, while c indicates OFF ACON,PCON Inputresister ACON,PCON Outputresister Hexadecimal dataPLC

Strany 187

4. SCON-CA259(Example iv) Set value = “3” z indicates ON, while c indicates OFF SCON Inputresister SCON Outputresister Hexadecimal dataPLC:OutputCHPL

Strany 188

4. SCON-CA260z IP address (No. 140: NADR) Specify the IP address in parameter No. 140. Setting range: 0.0.0.0 to 255.255.255.255 (Factory setting:

Strany 189

4. SCON-CA2614.10 Troubleshooting z Alarm messages and causes/actions When an alarm occurs, a corresponding simple alarm code is indicated by the

Strany 190

2. ACON-C/CG, PCON-C/CG192.5.4 Setting the Subnet Mask Set parameter No. 141, “SNMK: Subnet mask.” Set the same value you have set in the master

Strany 191

5. Appendix262OMRONPLCIAI RC controller Switching hubLAN cable LAN cable 5. Appendix Examples of connection settings with Omron’s master and Keyenc

Strany 192

5. Appendix2635.1.3 Setting the PLC (1) [CX-Programmer] [1] Set “NODE No.” rotary switches “x161” and “x160” to “0” and “A,” respectively, on the

Strany 193

5. Appendix264[6] In the “PLC I/O Table” window, double-click “Built-in Ports/Inner Boards” and then double-click “[1500] CJ2M-EIP21.” [7] In the “C

Strany 194

5. Appendix2655.1.4 Setting the PLC (2) [Network Configurator] [1] Start Network Configurator and click the [Connect] button on the toolbar to con

Strany 195

5. Appendix266[4] Right-click each device in the main window and select [Change Node Address] in the pop-up menu to set the IP address.

Strany 196

5. Appendix267PLC’s IP Address Controller’s IP Address

Strany 197

5. Appendix268[5] Double-click “Anybus-CC EtherNet/IP” in the main window and set the controller device parameters as follows: Item Set value 0001

Strany 198

5. Appendix269[7] Once the device is registered, “Anybus-CC EtherNet/IP” moves to “List of Registered Devices.” Double-click “Anybus-CC EtherNet/IP”

Strany 199

5. Appendix270[8] In the “Assign Connection” dialog box, click the [Edit Tag Set] button next to “Input Tag Set” in the Originator Device area.

Strany 200

5. Appendix271[9] In the “Edit Tag Set” dialog box, click the [Edit Tag] button. [10] In the “Edit Tag” dialog box, click the [New] button.

Strany 201

2. ACON-C/CG, PCON-C/CG202.6 Communicating with the Master Station 2.6.1 Operation Modes and Corresponding PLC I/O Areas The addresses allocated for

Strany 202

5. Appendix272[11] In the “Set Tag” dialog box, set as follows and click the [Register] button. [12] When tag “W0’” has been registered in the “Se

Strany 203

5. Appendix273[14] In the “Assign Connection” dialog box, set as follows and click the [Register] button. Confirm that the values in the “Target De

Strany 204

5. Appendix274[17] Upon establishment of link, the LEDs on the PLC and controller change their statuses as follows: LED statuses on PLC LED status

Strany 205

5. Appendix2755.1.5 Checking the I/O Data on the PLC [1] Start CX-Programmer. [2] Click the [Switch Watch Window] button on the toolbar. [3]

Strany 206

5. Appendix276PLCIAI RC controller Switching hubLAN cable LAN cable 5.2 Example of Connection Settings with Keyence’s Master The following devices

Strany 207

5. Appendix2775.2.3 Setting the PLC [1] Start Keyence’s ladder support software “KV-STUDIO.” [2] Start the Unit Editor and set the baud rate, IP

Strany 208

5. Appendix278[4] When the device is registered in the tree below the PLC, the “Default Adapter Settings” dialog box appears. Set the IP address and

Strany 209

5. Appendix279[6] In the “Set Connection” dialog box, set the connection type and send trigger. Select “Point-to-Point” for the connection type for b

Strany 210

5. Appendix280[8] Click the “Assign Device” button in the “Set Connection” dialog box to open the “Set Devices” dialog box. In this dialog box, set t

Strany 211

5. Appendix281[10] Click the “Apply” button in the bottom right-hand corner of the “Unit Editor” to update the EtherNet/IP setting information. Next,

Strany 212

2. ACON-C/CG, PCON-C/CG21x ACON/PCON outputoPLC input side (* “n” indicates the first input address of each axis.) DO on the ACON or PCON side and ou

Strany 213

5. Appendix2825.2.4 Checking the I/O Data on the PLC [1] Start KV-STUDIO in the “Monitor Mode.” [2] In the “Workspace” window, right-click “Anybu

Strany 214

Change History283Change History Revision date Description of revision February 2011 November 2011 June 2012 November 2012 First edition Second edit

Strany 217

Manual No.: ME0278-4B (November 2012)The information contained in this document is subject to change without notice for purposes ofproduct improvement

Strany 218

Please Read Before Use Thank you for purchasing our product. This operation manual explains the handling methods, structure and maintenance of this pr

Strany 219

2. ACON-C/CG, PCON-C/CG222.6.2 Remote I/O Mode (Number of Occupied Bytes: 2) In this operation method, EtherNet/IP communications is used to mimic th

Strany 220

2. ACON-C/CG, PCON-C/CG23(1) PLC address configuration (* “n” indicates the first address of each axis.) Parameter No.84ACON/PCON side DI (Port No.

Strany 221

2. ACON-C/CG, PCON-C/CG24(3) I/O signal assignment The controller's I/O port signal varies depending on the parameter No. 25 setting. (Refer to

Strany 222

2. ACON-C/CG, PCON-C/CG25 ACON Parameter No. 25 setting 512-point mode Electromagnetic valve mode 1 Electromagnetic valve mode 23 4 5 Category

Strany 223

2. ACON-C/CG, PCON-C/CG26 PCON Parameter No. 25 setting Positioning mode Teaching mode 256-point mode 0 1 2 Category PortNo.Symbol Signal name

Strany 224

2. ACON-C/CG, PCON-C/CG27 PCON Parameter No. 25 setting 512-point mode Electromagnetic valve mode 1 Electromagnetic valve mode 23 4 5 Category P

Strany 225

2. ACON-C/CG, PCON-C/CG282.6.3 Position/Simplified Direct Value Mode (Number of Occupied Bytes: 8) In this operation mode, EtherNet/IP communication

Strany 226

2. ACON-C/CG, PCON-C/CG29(2) I/O signal allocation for each axis The I/O signals of each axis consist of four input words (4 words = 8 bytes) and fou

Strany 227

2. ACON-C/CG, PCON-C/CG30PLC input Address (* “n” indicates the first input address of each axis.) When the current position is shown using the negati

Strany 228

2. ACON-C/CG, PCON-C/CG31(3) I/O signal assignment (* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Sy

Strany 230

2. ACON-C/CG, PCON-C/CG32(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents Details Cur

Strany 231

2. ACON-C/CG, PCON-C/CG332.6.4 Half Direct Value Mode (Number of Occupied Bytes: 16) This is the operation mode with the target position, positioning

Strany 232

2. ACON-C/CG, PCON-C/CG34(2) I/O signal allocation for each axis The I/O signals of each axis consist of one input word (8 words = 16 bytes) and one

Strany 233

2. ACON-C/CG, PCON-C/CG35PLC output Address (* “n” indicates the first output address of each axis.) When the target position is shown using the negat

Strany 234

2. ACON-C/CG, PCON-C/CG36PLC input Address (* “n” indicates the first input address of each axis.) When the current position is shown using the negati

Strany 235

2. ACON-C/CG, PCON-C/CG37(3) I/O signal assignment (* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Sy

Strany 236

2. ACON-C/CG, PCON-C/CG38(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents DetailsPres

Strany 237

2. ACON-C/CG, PCON-C/CG39(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents Details Cur

Strany 238

2. ACON-C/CG, PCON-C/CG402.6.5 Full Direct Value Mode (Number of Occupied Bytes: 32) This is the operation mode with all the values (target position,

Strany 239

2. ACON-C/CG, PCON-C/CG41(2) I/O signal allocation for each axis The I/O signals of each axis consist of one input word (16 words = 32 bytes) and one

Strany 240

Table of Contents Safety Guide...

Strany 241

2. ACON-C/CG, PCON-C/CG42PLC output Address (* “n” indicates the first output address of each axis.) When the target position is shown using the negat

Strany 242

2. ACON-C/CG, PCON-C/CG43Address (* “n” indicates the first output address of each axis.) When the zone boundary is shown using the negative figure, i

Strany 243

2. ACON-C/CG, PCON-C/CG44PLC input Address (* “n” indicates the first input address of each axis.) When the current position is shown using the negati

Strany 244

2. ACON-C/CG, PCON-C/CG45(3) I/O signal assignment (* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Sy

Strany 245

2. ACON-C/CG, PCON-C/CG46(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Address Bit Symbol Function DetailsAccelera

Strany 246

2. ACON-C/CG, PCON-C/CG47(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Address Bit Symbol Function Detailsb5b4-Una

Strany 247

2. ACON-C/CG, PCON-C/CG48(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.) Signal type Bit Symbol Contents DetailsCurr

Strany 248

2. ACON-C/CG, PCON-C/CG492.6.6 Remote I/O Mode 2 (Number of Occupied Bytes: 12) In this operation method, EtherNet/IP communications is used to mimic

Strany 249

2. ACON-C/CG, PCON-C/CG50(1) PLC address configuration (* “n” indicates the first address of each axis.) Parameter No.84ACON/PCON side DI and input

Strany 250

2. ACON-C/CG, PCON-C/CG51PLC input Address (* “n” indicates the first input address of each axis.) When the current position is shown using the negati

Strany 251

3.6 Communicating with the Master Station...933.6.1 Operation Modes

Strany 252

2. ACON-C/CG, PCON-C/CG52(3) I/O signal assignment For the signal assignments corresponding to each PIO pattern, refer to the I/O signal assignments

Strany 253 - 4.7 I/O Signal Timings

2. ACON-C/CG, PCON-C/CG532.6.7 I/O Signal Controls and Function * ON indicates that the applicable bit signal is “1”, while OFF indicates that the bi

Strany 254 - 4.8 Operation

2. ACON-C/CG, PCON-C/CG54(5) Servo ON command (SON) PLC output signal Operation preparation end (SV) PLC input signal When the SON signal is turn

Strany 255

2. ACON-C/CG, PCON-C/CG55(6) Home return (HOME) PLC output signal Home return completion (HEND) PLC input signal Under home return operation (GH

Strany 256

2. ACON-C/CG, PCON-C/CG56(7) Positioning start (CSTR): Used in the position/simple direct mode PLC output signal This signal is processed at the star

Strany 257

2. ACON-C/CG, PCON-C/CG57TravelSpeedPositioning band TimeTarget position Timing at which the position complete signal turns ON (10) Positioning comple

Strany 258

2. ACON-C/CG, PCON-C/CG58Zone signal+ direction Actuator operation Home Zone setting -Zone setting +(12) Zone 1 (ZONE1) PLC input signal Zone 2

Strany 259

2. ACON-C/CG, PCON-C/CG59(13) +Jog (JOG+) PLC output signal –Jog (JOG–) PLC output signal This signal is the command for the jog operation startup

Strany 260

2. ACON-C/CG, PCON-C/CG60(14) Jog-speed/inch-distance switching (JVEL) PLC output signal This change-over signal is used for the parameters specifyin

Strany 261 - Speed n3

2. ACON-C/CG, PCON-C/CG61(16) Teaching mode command (MODE) PLC output signal Teaching mode signal (MODES) PLC input signal When the MODE signal is

Strany 262

5.2 Example of Connection Settings with Keyence’s Master ... 2765.2.1 Connection Example ...

Strany 263

2. ACON-C/CG, PCON-C/CG62SpeedTravelPositioning band Positioning band Positioning band DIR = OFF Target position DIR = ON (19) Operating mode selector

Strany 264

2. ACON-C/CG, PCON-C/CG63(23) Pressing and a miss (PSFL) PLC input signal In the case that the pressing operation was performed, and the actuator mo

Strany 265

2. ACON-C/CG, PCON-C/CG64(26) Load output judgment (LOAD) PLC input signal Dedicated PCON function This signal is available only in the pressing opera

Strany 266

2. ACON-C/CG, PCON-C/CG65Target positionTravelSpeedPosition where the actuator is pushed against the work part and the pressing completion is judged s

Strany 267

2. ACON-C/CG, PCON-C/CG66(28) Stopping control mode (SMOD) PLC output signal Dedicated PCON function One of the pulse motor general characteristics

Strany 268

2. ACON-C/CG, PCON-C/CG67Setting: 50 Setting: 100Setting: 10 (29) Acceleration/deceleration mode (MOD1ޔMOD0) PLC output signal Dedicated ACON function

Strany 269 - 4.10 Troubleshooting

2. ACON-C/CG, PCON-C/CG68Caution: [1] Even if a position command or direct value command with S-shaped motion setting is issued when the actuator is

Strany 270 - 5.1.1 Connection Example

2. ACON-C/CG, PCON-C/CG69(30) Stop Mode Selection (ASO1, ASO0) PLC Output Signal Select the stop mode for the duration before the movement to the n

Strany 271 - 5. Appendix

2. ACON-C/CG, PCON-C/CG70PLC sequence programControl signalStatus signalACON, PCONControl signalStatus signalMaster station o Slave transmission

Strany 272

2. ACON-C/CG, PCON-C/CG712.8 Operation The timings for the basic operation examples in the Position/Simplified Direct Value Mode, Half direct value m

Strany 274

2. ACON-C/CG, PCON-C/CG72* T1: Considering the scanning time of the host controller, set it so that “T1  0ms”. * Yt+Xt  tdpf  Yt+Xt+3 (msec) [7][1

Strany 275 - Controller’s IP Address

2. ACON-C/CG, PCON-C/CG73(2) Operation in the half direction mode It is operated with the data set in the PLC's target position register, positi

Strany 276

2. ACON-C/CG, PCON-C/CG74*T1: Considering the scanning time of the host controller, set it so that “T1  0ms”. *Yt+Xt  tdpf  Yt+Xt+3(msec) Position

Strany 277

2. ACON-C/CG, PCON-C/CG75(3) Operation in the full direct mode The actuator is operated by specifying all conditions required for positioning such as

Strany 278 - Originator Device area

2. ACON-C/CG, PCON-C/CG76[1][2][3][4][5][6][7][8]Set value of target position data Set value of positioning band data Set value of speed data Set valu

Strany 279

2. ACON-C/CG, PCON-C/CG77*T1: Considering the scanning time of the host controller, set it so that “T1  0ms”. *Yt+Xt  tdpf  Yt+Xt+3 (msec) [9][10]

Strany 280

2. ACON-C/CG, PCON-C/CG78[1][2][3]Actuator speed Speed n2 Speed n3 Set value of speed or acceleration/deceleration (4) Data change during movement In

Strany 281

2. ACON-C/CG, PCON-C/CG792.9 EtherNet/IP Related Parameters Parameters relating to EtherNet/IP are No. 84, No. 86 to 87, No. 90 and No. 140 to 142. C

Strany 282

2. ACON-C/CG, PCON-C/CG80z Network type (No.87 NTYP) The network module type is set for the parameter No. 87. Do not change the default value. z Fie

Strany 283

2. ACON-C/CG, PCON-C/CG81(Example ii) Set value = “1” z indicates ON, while c indicates OFF ACON,PCON Inputresister ACON,PCON Outputresister Hexadeci

Strany 284 - 5.2.1 Connection Example

1Safety Guide “Safety Guide” has been written to use the machine safely and so prevent personal injury or property damage beforehand. Make sure to rea

Strany 285 - 5.2.3 Setting the PLC

2. ACON-C/CG, PCON-C/CG82(Example iii) Set value = “2” z indicates ON, while c indicates OFF ACON,PCON Inputresister ACON,PCON Outputresister Hexadec

Strany 286

2. ACON-C/CG, PCON-C/CG83(Example iv) Set value = “3” z indicates ON, while c indicates OFF ACON,PCON Inputresister ACON,PCON Outputresister Hexadeci

Strany 287

2. ACON-C/CG, PCON-C/CG84z IP address (No. 140: IPAD) Specify the IP address in parameter No. 140. Setting range: 0.0.0.0 to 255.255.255.255 (Fac

Strany 288

3. SCON-CA/CFA853. PCON-CA/CFA 3.1 Operation Modes and Functions PCON-CA/CFA controllers equipped with EtherNet/IP can be operated in the following

Strany 289

3. SCON-CA/CFA86[2] Position/simplified direct value mode: In this operation mode, EtherNet/IP communication is used to select and command movement

Strany 290

3. SCON-CA/CFA87[4] Full direct value mode: In this operation mode, all values regarding position control (“Target Position,” "Speed” and "

Strany 291 - Change History

3. SCON-CA/CFA883.2 Model Numbers The Model numbers of PCON-CA/CFA applicable to EtherNet/IP are described as follows. Ɣ PCON-CA--EP-Ɣ PCON-CFA-

Strany 292

3. SCON-CA/CFA893.3 EtherNet/IP Interface 3.3.1 Names of the Parts The names of each section related to EtherNet/IP are described as follows. 3.3.2

Strany 293

3. SCON-CA/CFA90813.4 Wiring Example 3.4.1 Connection Diagram * Ethernet cable: Straight cable of category 5e or above, 100 m max (Aluminum tape an

Strany 294 - 12.11.000

3. SCON-CA/CFA913.5 Setting Using the teaching tool, set controller parameters. Set the mode toggle switch on the front panel of the controller to “M