X-SEL ControllerRC Gateway FunctionOperation Manual Fifth EditionSIO Type XSEL- P/Q/PX/QX R/S/RX/SXRXD/SXDFieldbus Type

Strany 2

4No.OperationDescription Description 4 Installation and Start(4) Safety Measures Ɣ When the work is carried out with 2 or more persons, make it clea

Strany 3 - Please Read Before Use

5. Program Creating943) The RC PC software is started. Click Position, click Edit/Teaching, and then select the axis number of the axis whose data

Strany 4

5. Program Creating95(4) Editing a program Follow the procedure below to edit a program: 1) Click Controller, point to Reconnect, and then select OK

Strany 5 - Table of Contents

5. Program Creating965) Next, enter the program. Since the actuator is operated continuously between position Nos. 0 and 1 in this example, the progr

Strany 6

5. Program Creating975.3 Program Language Used by the RC Gateway 5.3.1 List of Program Language Commands A list of program language (SEL language) c

Strany 7 - Safety Guide

5. Program Creating98Ɣ Reference: Relationships between Existing SEL Commands and RC Gateway FunctionThe relationships between the RC gateway functi

Strany 8

5. Program Creating99Command category Commands How each command is affected by RC gateway function String operation SCPY, SCMP, SGET, SPUT, STR, STRH

Strany 9

5. Program Creating100 5.3.2 Explanation of Commands (1) Position data operation commands X-SEL ż: Valid z RPGT (Read RC axis position data)

Strany 10

5. Program Creating101 X-SEL ż: Valid z RPPT (Write RC axis position data) RC position data mode RC ×: Invalid(Note 1)Command, declaration Exte

Strany 11

5. Program Creating102 X-SEL ż: Valid z RPCR (Clear RC axis position data) RC position data mode RC ×: Invalid(Note 1)Command, declaration Ext

Strany 12

5. Program Creating103 X-SEL ż: Valid z RPCP (Copy RC position data) RC position data mode RC ×: Invalid(Note 1)Command, declaration Extension

Strany 13 - Alert Indication

5No.OperationDescription Description 6 Trial Operation Ɣ When the work is carried out with 2 or more persons, make it clear who is to be the leader

Strany 14

5. Program Creating104 X-SEL ż: Valid z RPRD (Read current RC axis position) RC position data mode RC ×: Invalid(Note 1)Command, declaration E

Strany 15 - Precautions in Handling

5. Program Creating105X-SEL ż: Valid z RPRQ (Read current RC axis position [direct reading of 1 axis]) RC position data mode RC ż: Valid Command, decl

Strany 16 - Starting procedures

5. Program Creating106 X-SEL ż: Valid z RPVL (Write RC axis speed data) RC position data mode RC ×: Invalid(Note 1)Command, declaration Extens

Strany 17 - 1. Control Method Overview

5. Program Creating107X-SEL ż: Valid z RPAD (Write RC axis acceleration/deceleration data) RC position data mode RC ×: Invalid(Note 1)Command, decla

Strany 18 - 1.1 Communication system

5. Program Creating108 X-SEL ż: Valid z RPIP (Write RC axis positioning band data) RC position data mode RC ×: Invalid(Note 1)Command, declaration

Strany 19 - 1. Outline of Control Method

5. Program Creating109X-SEL ż: Valid z RPTQ (Write RC axis current-limiting value data during push-motion operation) RC position data mode RC ×: Inv

Strany 20 - 1.2 Operation system

5. Program Creating110 X-SEL ż: Valid z RGVL (Read RC axis speed data) RC position data mode RC ×: Invalid(Note 1)Command, declaration Extension c

Strany 21 - 1.3.1 For SIO type

5. Program Creating111 X-SEL ż: Valid z RGIP (Read RC axis positioning band data) RC position data mode RC ×: Invalid(Note 1)Command, declaration E

Strany 22 - 1.Outline of Control Method

5. Program Creating112 (2) Operation commands X-SEL ż: Valid z RAXS (Set RC axis pattern) RC position data mode RC ż: Valid Command, declaration E

Strany 23

5. Program Creating113 X-SEL ż: Valid z RSON (Turn ON RC axis servo) RC position data mode RC ż: Valid Command, declaration Extension condition (LD,

Strany 24

6No.OperationDescription Description 8 Maintenance and Inspection Ɣ When the work is carried out with 2 or more persons, make it clear who is to be

Strany 25 - No color

5. Program Creating114 X-SEL ż: Valid z RHOM (Return RC axis to home) RC position data mode RC ż: Valid Command, declaration Extension condition (L

Strany 26 - 2. Specification

5. Program Creating115 X-SEL ż: Valid z RMVP (Move RC axis via position specification) RC position data mode RC ż: Valid Command, declaration Extens

Strany 27 - 2.1.2 Teaching Tool

5. Program Creating116 X-SEL ż: Valid (Note 2)z RMPI (Move RC axis incrementally) RC position data mode RC ×: Invalid(Note 1)Command, declaration

Strany 28 - 2. Specication

5. Program Creating117X-SEL ż: Valid z RMVD (Move RC axis via absolute direct-value position specification) RC position data mode RC ×: Invalid(Not

Strany 29 - 2.2 Fieldbus type

5. Program Creating118 X-SEL ż: Valid (Note 2)z RMDI (Move RC axis via incremental direct-value position specification) RC position data mode RC ×:

Strany 30

5. Program Creating119 X-SEL ż: Valid z RPUS (Move RC axis via push-motion operation) RC position data mode RC ×: Invalid(Note 1)Command, declarati

Strany 31

5. Program Creating120 X-SEL ż: Valid z RSTP (Stop RC axis movement) RC position data mode RC ż: Valid Command, declaration Extension condition (LD

Strany 32 - A/PCON, SCON-CA

5. Program Creating121(3) Information read commands X-SEL ż: Valid z RCST (Read RC axis status) RC position data mode RC ż: Valid Command, declara

Strany 33 - 3.1 Notes on Wiring

5. Program Creating122 5.4 Notes on Resuming Interrupted Operation If any RC axis movement specified in a SEL program was interrupted and then the op

Strany 34 - 3.2 Wiring method

5. Program Creating1235.5 Checking the Completed Position (Positioning Band) In the “Method to use position data in X-SEL”, whether or not the positi

Strany 35 - 3. Wiring

7Alert Indication The safety precautions are divided into “Danger”, “Warning”, “Caution” and “Notice” according to the warning level, as follows, and

Strany 36

5. Program Creating124 Program examples x Main program Step E N Cnd Cmnd Operand1 Operand2 Pst Comment 1 RAXS 0 10000 2 TAG

Strany 37 - (Except for SCON)

5. Program Creating125x Subroutine 1 Step E N Cnd Cmnd Operand1 Operand2 Pst Comment 34 //-------------------------------------------- 35 // Ob

Strany 38 - Not required if a

6. Appendix126 6. Appendix 6.1 List of Additional I/O Parameters The shaded parameters in bold are new parameters. For the parameters in the X-SEL

Strany 39

6. Appendix127I/O parameters (The shaded parameters in bold are new parameters: Continued) No. Parameter name Defaultvalue(reference)Input range Unit

Strany 40

6. Appendix128 I/O parameters (The shaded parameters in bold are new parameters: Continued) No. Parameter name Defaultvalue(reference)Input range Uni

Strany 41

6. Appendix129I/O parameters (The shaded parameters in bold are new parameters: Continued) No. Parameter name Defaultvalue(reference)Input range Unit

Strany 42

6. Appendix130 I/O parameters (The shaded parameters in bold are new parameters: Continued) No. Parameter name Defaultvalue(reference)Input range Uni

Strany 43

6. Appendix131I/O parameters (The shaded parameters in bold are new parameters: Continued) No. Parameter name Defaultvalue(reference)Input range Unit

Strany 44

6. Appendix132 6.2 Troubleshooting for Communication 6.2.1 Error Code List Level No. Error name Description/action 220 RC axis multiple-use erro

Strany 45

6. Appendix133Level No. Error name Description/action 405 RC Gateway Communication Classification Error (SEL) An operation cannot be made with the

Strany 47

6. Appendix134 Level No. Error name Description/action 438 RC position number error (SEL) The RC position number is not specified correctly. o Che

Strany 48

6. Appendix135Level No. Error name Description/action 6A0 UBM flash ROM status error The data in the user-data backup memory is not correctly w

Strany 49

6. Appendix136 Level No. Error name Description/action 6AC RC axis control JOB logic error A logic error occurred in the RC axis control JOB. o Co

Strany 50 - (Except for SCON-CA)

6. Appendix137Level No. Error name Description/action 6CC RC Gateway simultaneous use errorBoth SIO Type and Fieldbus Type turned effective. oThey

Strany 51

6. Appendix138 6.2.2 Troubleshooting x Condition: Communication cannot be performed properly! Follow the flowchart to identify the applicable cause

Strany 52 - 4.1 Setting Procedure

6. Appendix139New system started? (Here, a new system includes a system that has been assembled anew based on an existing design.) [1] Invalid axis

Strany 53 - 䎃13 (the decimal system)

6. Appendix140 Communication is disabled with a certain controllero[1]Terminal resistor not connected o[2] Wrong setting in the slave input

Strany 54

6. Appendix141Communication occasionally disabled? o [[1] Check if the wiring route of the communication cable has been changed] *5 [[2] Check if e

Strany 55

6. Appendix142 *1 Disconnect the X-SEL communication cable from J3 (D-sub, 9-pin connector) on the SIO converter and connect the RC PC software (RCM-

Strany 56

6. Appendix143[3] Click Position, and then select Edit/Teaching.The position data edit axis select window appears and the connected axes are listed a

Strany 57 - 4.2 Settings for SIO type

9Precautions in Handling 1. Sending an address or a function that is not mentioned in this manual may disable the ROBO Cylinder from operating normal

Strany 58

6. Appendix144 *2 Check the wiring again by referring chapter of this manual. *3 Check the axis No. setting again by referring chapter of this manua

Strany 59

6. Appendix1456.3 Adding the Gateway Function to Existing XSEL-P/Q/PX/QX ControllersIf the gateway function is to be added to an existing XSEL contro

Strany 60

Change History146 Change History Revision date Revision description 2007.11 Released the first edition Second edition x Page 2 : Added note stati

Strany 62

Manual No.: ME0188-5A (September 2012)The information contained in this document is subject to change without notice for purposes of product improveme

Strany 63 - MODE Switch

10Starting procedures YesYesInstallation and Wiring (Chapter 3)Have the actuators and controllers installed and connected following the instructions i

Strany 64

1. Outline of Control Method111. Control Method Overview RC Gateway Function (SIO Type and Fieldbus Type) enables an operation in the network with th

Strany 65 - [Procedures 5] Rebooting

1.Outline of Control Method121.1 Communication system RC Gateway Function can be selected from two types of communication systems and two types of op

Strany 66

1. Outline of Control Method13[2] For Fieldbus type (DeviceNet Communication system) Connect an X-SEL controller and slaves (RC controllers) with Dev

Strany 68

1.Outline of Control Method141.2 Operation system [1] To use position data in X-SEL It is the method to perform operation using the RC position data

Strany 69

1. Outline of Control Method151.3 Name and Function of Each Part Relating to RC Gateway Function 1.3.1 For SIO type (1) XSEL-P/Q/PX/QX [1] +5V sup

Strany 70

1.Outline of Control Method16(2) XSEL-R/S/RX/SX/RXD/SXD [1] System Operation Setting Switches These are switches to set the operation mode of the sy

Strany 71 - Rotary Switch

1. Outline of Control Method171.3.2 For Fieldbus type (option) (1) XSEL-P/Q/PX/QX In the case of XSE-P/Q/PX/QX, the fieldbus board for the Gateway i

Strany 72

1.Outline of Control Method18[1] Monitor LEDs NS MSScannerModeThe conditions of the slaves (each controller) and the network can be checked with the

Strany 73

1. Outline of Control Method19[3] Fieldbus connector Connect the slaves (IAI controllers applicable for RC Gateway Fieldbus Type) to X-SEL. (Note) RC

Strany 74

2. Specication202. Specification 2.1 SIO type 2.1.1 Communication type Item Specification Transmission path structure IAI’s dedicated multi-drop

Strany 75

2. Specication212.1.2 Teaching Tool For XSEL-P/Q/PX/QX (Note 1)Teaching tool name Model Applicable versions RC PC Software Parameter Configuration

Strany 76

2. Specication222.1.4 Input and Output Timing (SIO Type) The response time (Time it takes RC controller to respond back to XSEL controller's qu

Strany 77

2. Specication232.2 Fieldbus type 2.2.1 Communication type Item SpecificationTransmission path structure IAI’s dedicated differential communicatio

Strany 78

Please Read Before Use Thank you for purchasing our product. This Operation Manual explains the handling methods, structure and maintenance of this pr

Strany 79

2. Specication242.2.3 Operation Manuals Related to This Product No. Name Manual No. 1 Operation Manual for XSEL-P/Q controller ME0148 2 Opera

Strany 80

2. Specication252.2.4 Input and Output Timing (Fieldbus Type) The response time (Time it takes RC controller to respond back to XSEL controller&apos

Strany 81

2. Specication26MSEP, MSCON Xt YtFtFtMtMtX-SEL Controller MSEPMSCON Controller Command processing time (Operating time, etc.) MSEPControl Signal(MSCO

Strany 82

3. Wiring273. Wiring 3.1 Notes on Wiring [1] Provide noise elimination measures for the electrical devices located along the same power-supply path

Strany 83

3. Wiring283.2 Wiring method RC gateway function has SIO type and Fieldbus type. Wiring method and necessary equipment differ between each type. Refe

Strany 84

3. Wiring293.2.1 Wiring Method of SIO type [1]-1 Wiring diagram (Example 1: When SIO converter is used for XSEL-P/Q/PX/QX) RUN/ALMEMGTC10ERRORSTATUS

Strany 85

3. Wiring30SIO communication components required by the configuration shown in Example 1 Name Model QuantitySIO converter RCB-TU-SIO-A or B 1 Po

Strany 86

3. Wiring31[1]-2 Connection diagram (Example 1: When SIO converter is used for XSEL-P/Q/PX/QX) RS232C cable (cross) XSELCDRDSDERSGDRRSCS+5V1234567891

Strany 87 - Make Byte Swap ineffective

3. Wiring32SGA SASBSGSGBGNDHK-SB/20276×2P×AWG222P×AWG22HK-SB/20276×LROBONET_GatewayR_SIOSCON-CMC1.5/4-ST-3.5121234123123127Recommended cable 1 Recomme

Strany 88

3. Wiring33[2]-1 Wiring diagram (Example 2: When RS232 conversion unit is used for XSEL-P/Q/PX/QX) Caution: Use a common 0V line for the 24V power s

Strany 90 - 5. Program Creating

3. Wiring34Components required by the configuration shown in Example 2 Name Model QuantityRS232 conversion unit RCB-CV-GW 1 Communication cable

Strany 91

3. Wiring35[2]-2 Circuit diagram (Example 2: When RS232 conversion unit is used for XSEL-P/Q/PX/QX) CB-RCB-SIO[1] A (4-1473562-4 by AMP)CB-ERC2-CTL00

Strany 92

3. Wiring36[3]-1 Wiring drawing (Example 3: When RS232 conversion unit is used to connect only 1 axis for XSEL-P/Q/PX/QX)SV/ALMSIOPCMOTBKMPO24VEMG-MP

Strany 93

3. Wiring37[4]-1 Wiring diagram (Example 4: When connecting to XSEL-R/S/RX/SX/RXD/SXD) Caution: Use a common 0V line for the 24V power supply for ea

Strany 94

3. Wiring38Components required by the configuration shown in Example 4 Name Model QuantityPower I/O Cable for SIO type CB-ERC2-PWBIO-ƑƑƑ 1 Netwo

Strany 95

3. Wiring39[4]-2 Circuit diagram (Example 4: When connecting to XSEL-R/S/RX/SX/RXD/SXD) [1] A (4-1473562-4 by AMP)CB-ERC2-CTL001CB-RCB-CTL002ERC2-SES

Strany 96

3. Wiring40[5] SIO converter for X-SEL and RC controller connection (RCB-TU-SIO) This is a RS232C  RS485 converter. 1) D-sub, 9-pin connector This

Strany 97

3. Wiring41[6] Emergency stop system configuration example 24V0VTeaching pendantEMG2MCEmergency stop release switchPORTswitchEMG1Emergency stop switc

Strany 98

3. Wiring423.2.2 Wiring Method of Fieldbus type [1]-1 Wiring Caution Prepare the peripheral devices for DeviceNet (T-junction tap, cable, etc.) sepa

Strany 99 - PC software

3. Wiring43 Components Necessary to Construct Layout in Example The following is just an example. Prepare the wiring components dedicated for DeviceN

Strany 100 - 5. Program Creating

Table of Contents Safety Guide...1Pre

Strany 101

3. Wiring44[1]-2 Connection diagram Caution: Use a common 0V line for the 24V power supply for each controller. (Except for SCON-CA) [1] ADC-N1-4R12

Strany 102

3. Wiring45[2] Emergency stop system configuration example x To comply with the safety categories, make sure to follow the instructions in the instr

Strany 103

4. RC Gateway Function setting464. RC Gateway Function setting 4.1 Setting Procedure Conduct the settings for the master (X-SEL) and the slaves (axi

Strany 104 - Function

4. RC Gateway Function setting474.1.1 Before Starting Setup (Regarding Binary and Hexadecimal Numbers) Inputting parameters of RC Gateway setting are

Strany 105

4. RC Gateway Function setting484.1.2 Master (X-SEL) Settings 1 (In common for Fieldbus type and SIO type) The setting should be conducted following

Strany 106

4. RC Gateway Function setting49[Procedure 1] Operation method setting Select using position data in from the master (X-SEL) controller memory or sla

Strany 107

4. RC Gateway Function setting50[Procedure 3] Setting of number of used positions (Set this only in method to use position data in X-SEL) Set the num

Strany 108

4. RC Gateway Function setting514.2 Settings for SIO type 4.2.1 Master (X-SEL) Setting 2 Continued from the previous page, X-SEL PC software is used

Strany 109

4. RC Gateway Function setting52[Procedure 2] Reflection of changed parameters Click the parameter send button to send the changed parameters to X-SE

Strany 110

4. RC Gateway Function setting534.2.2 Slave (axis to be controlled) Setting (SCON-C, PCON-SE, ACON-SE, ERC2-SE, ROBONET) (1) SCON-C, PCON-SE, ACON

Strany 111

5.3Program Language Used by the RC Gateway ... 975.3.1 List of Program Language Co

Strany 112

4. RC Gateway Function setting54[Procedure 1] Axis No. Setting The setting of the axis numbers differ for each SCON-C, PCON-SE, ACON-SE and ERC2-SE.I

Strany 113

4. RC Gateway Function setting55[Procedure 2] Display of Parameter Setting Window Start the RC PC software, click Parameter, and then click Edit.[Pro

Strany 114

4. RC Gateway Function setting56[Procedures 5] Reflection of Changed Parameters After writing the parameter by clicking the parameter writing button,

Strany 115

4. RC Gateway Function setting57(2) For ROBONET * Refer to (1) in this section for SCON-C, PCON-SE, ACON-SE and ERC2-SE. The setting of ROBONET is to

Strany 116

4. RC Gateway Function setting58[Procedures 2] Writing the Set Baud Rate Click Write button and then Yes.[Procedures 3] Setting of User Setting Swit

Strany 117

4. RC Gateway Function setting59[Procedures 5] Rebooting Set the MODE switch on the front panel of GateWayR Unit to AUTO side. Re-input the power to

Strany 118

4. RC Gateway Function setting604.3 Settings for Fieldbus type 4.3.1 Master (X-SEL) Setting 2 X-SEL PC software is used in the setting process. [Pro

Strany 119

4. RC Gateway Function setting61[Procedure 3] Setting for controller definition on slave (axis to be controlled)Have the settings for the constructio

Strany 120

4. RC Gateway Function setting62No. I/O Parameter Unit Set Value Defaultfactory setting432Fieldbus Slave 0 Construction Definition (Registration of

Strany 121

4. RC Gateway Function setting63No. I/O Parameter Unit Set Value Defaultfactory setting443Fieldbus Slave 11 Construction Definition (Registration of

Strany 122

1Safety Guide “Safety Guide” has been written to use the machine safely and so prevent personal injury or property damage beforehand. Make sure to rea

Strany 123

4. RC Gateway Function setting64[Procedure 4] Writing Process of Changed Parameters to Memory Click the parameter send button to send the changed par

Strany 124

4. RC Gateway Function setting654.3.2 Slave (axis to be controlled) Setting (1) In the case of PCON, ACON, SCON-CAThe setting of the slave axis cont

Strany 125

4. RC Gateway Function setting66[Procedure 2] Display of Parameter Setting Window Start the RC PC software, click Parameter, and then click Edit.[Pro

Strany 126

4. RC Gateway Function setting67[Procedure 5] Axis number and Node address setting Set the node address set in Section 4.3.1 [Procedure 3] to Paramet

Strany 127

4. RC Gateway Function setting68(2) MSEP The setting of MSEP is to be carried out with being connected to PC with the enclosed cable, and with using

Strany 128

4. RC Gateway Function setting693) Once the main window is open, click on Read button and then click Yes.[Procedure 2] Setting for Address Set th

Strany 129 - 1 200.00 75 0.3 0 0.5

4. RC Gateway Function setting70Example 2) When connecting PCON, MSEP, SCON-CA to a slave controller Model Code of Slave ControllerAddress setting va

Strany 130

4. RC Gateway Function setting71[Procedure 4] Setting for Number of Axes and Map Setting 1) Set the number of axes to be used. 2) For the map setting

Strany 131

4. RC Gateway Function setting72[Procedure 5] Swap setting 1) Click on Setting button and then click Specialty Parameter.2) Make BYTE swap “valid”

Strany 132 - 6. Appendix

4. RC Gateway Function setting73[Procedure 6] Parameter Writing Write the edited operation mode setting parameters to MSEP. Click on the Write button

Strany 133 - 6. Appendix

2No.OperationDescription Description 2 Transportation Ɣ When carrying a heavy object, do the work with two or more persons or utilize equipment such

Strany 134

4. RC Gateway Function setting74[Procedure 9] RC PC Software Startup Start up RC PC Software. [Refer to the operation manual of the PC software for t

Strany 135

4. RC Gateway Function setting754) The confirmation window for controller reboot opens. Click Yes.5) The operation pattern setting is required on

Strany 136

4. RC Gateway Function setting76(3) In case of MSCON The setting of MSCON is to be carried out with being connected to PC with the enclosed cable, an

Strany 137

4. RC Gateway Function setting773) The main screen will be displayed. When the Read button is pressed, the confirmation window opens. Click Yes.Once t

Strany 138 - 6.2.1 Error Code List

4. RC Gateway Function setting78Example 1) Two MSCONs are connected to the Slave ControllerSlave Controller Model No.Value set for Address(Node addre

Strany 139

4. RC Gateway Function setting79[Procedure 3] Setting of Top Axis Number Click “Setting (S)” ĺ “Unit Number” in the main window, and set the same num

Strany 140

4. RC Gateway Function setting80[Procedure 4] Operation Mode Setting and Occupation Information Confirmation 1) Select “Direct Value, Positioner Mode

Strany 141

4. RC Gateway Function setting81[Procedure 5] Set the byte 1) Setting ψ Click Special Parameters.2) Make Byte Swap effective.Make Byte Swap ineffe

Strany 142

4. RC Gateway Function setting82[Procedure 6] Parameter Writing Write the edited operation mode setting parameters to MSCON. Click on the Writebutton

Strany 143

4. RC Gateway Function setting83[Procedure 9] PIO Pattern Confirmation Confirm that the MSCON parameter No. 25 “PIO Pattern Selection” has been set t

Strany 144 - 6.2.2 Troubleshooting

3No.OperationDescription Description (2) Cable Wiring Ɣ Use our company’s genuine cables for connecting between the actuator and controller, and for

Strany 145

5. Program Creating845. Program Creating Operations are performed using a program that sets positioning data and determines the operation sequence an

Strany 146

5. Program Creating85Comparison table of two operation modes Key function Method to use RC position data in X-SELMethod to use RC position data in RCN

Strany 147

5. Program Creating86Comparison of Functions between Fieldbus type and SIO type (Different part limitation) Function Fieldbus type SIO type Safety

Strany 148

5. Program Creating875.1 Operation Using the X-SEL Position Data Mode An example of operation in which one RC controller is used to move an actuator

Strany 149

5. Program Creating882) Enter the following data, starting from position No. 0. z Pos (target position) [mm] Input the target position that the actu

Strany 150

5. Program Creating89(3) Editing a program Follow the procedure below to edit a program: 1) Click Program and then select Edit to open the program e

Strany 151 - Controllers

5. Program Creating903) Next, enter the program. Since it is a back and forth operation between Position No. 0 and No. 1, the detail of the program w

Strany 152 - Change History

5. Program Creating915.2 Operation with Method to Use Position Data in RC For Fieldbus Type, edit the position data of the RC controllers on each RC

Strany 153

5. Program Creating923) In the Baud Rate (bps) field, set the same value specified in the connection confirmation screen of the X-SEL PC software (re

Strany 154 - 12.09.000

5. Program Creating932) When the following screen appears, select both Start “PC Interface Software for RC” and Off-line Work (Port Close), and then